Solar sizing

Preliminary solar-system sizing

Estimate PV-array capacity, battery storage and inverter size using a clearer engineering basis than the previous calculator. This is a planning aid, not a final design.

Load & system inputs

Checking calculator access...
Method

What the calculator considers

PV is sized from daily energy, available solar resource and a performance ratio. Battery capacity uses autonomy, allowable depth of discharge and storage efficiency. Inverter size is based on estimated peak load plus operating margin.

  • 550 W planning module size
  • 75% overall PV performance ratio
  • 80% usable depth of discharge for LiFePO₄ or 50% for lead-acid
  • 25% inverter headroom with 0.9 planning power factor

Final equipment selection requires an appliance/load schedule, starting-current review, cable/protection design, roof/ground assessment, shading review and current equipment data.

Request a site survey / quotation

After calculating, send the result to the technical team with your contact details.